Level Controller
The controller maintains a constant oil level on the Separators at the desired set point by modulating the control valves downstream of Oil pumps. The control valves are fail open. The control output signal shall be direct acting and the control valve "OPDIR" is reverse.As the liquid falls below the setpoint, the controller shall close the control valve to increase the liquid level. High and low alarm shall be displayed on HMI.
Flow Controller
The controllers provide minimum flow control at required set point to protect each Oil pump by opening the control valve. The control valves are fail open. The control output signal shall be reverse acting and the control valve "OPDIR" is reverse.As the liquid falls below the setpoint, the controller shall open the control valve to increase the liquid level. High and low alarm shall be displayed on HMI.
Interface Level Controller
The controller maintains a constant oil-water interface level on the Separators at the desired set point by modulating the control valves downstream of Produce Water Hydroclyclones. The control valves are fail closed. The control output signal shall be direct acting and the control valve "OPDIR" is direct.As the liquid falls below the setpoint, the controller shall close the control valve to increase the liquid level. High and low alarm shall be displayed on HMI.
Oil pump shall be inhibited if the valve is in closed position