Pada 23 Maret .2005 jam 1:20 siang,
di BP Texas City refinery terjadi ledakan dan api yang mengakibatkan 15 orang
meninggal dunia dan menciderai 180 orang dengan kerugian material melebihi $1.5 billion.
Insiden terjadi ketika start-up isomerization unit, raffinate splitter tower
meluap. Pressure relief device terbuka yang menyebabkan flammable fluid keluar
dari blowdown stack yang tidak dilengkapi dengan flare. Keluarnya fluid ini
menyebabkan ledakan dan api. Fatality terjadi di kantor yang dekat lokasinya.
43.000 orang penduduk diperintahkan tetap didalam ruangan dan ledakan
mengakibatkan rumah-rumah dalam radius ¾ mile dari refiney
rusak.
Showing posts with label ESD system. Show all posts
Showing posts with label ESD system. Show all posts
Thursday, July 4, 2013
Thursday, May 30, 2013
Fail Safe Design Maintainability In Remote Platform?
Shutdown platform occurred during my site trip last year in one of the remote offshore wellhead platform. ESD alarm on the operating console showed that the shutdown is triggered by one of the push button on the cellar-deck.
The the problem comes, every time the operator wants to reset the ESD logic. The push button fail safe mode which in de-energized status keep sending shutdown command and it cannot be re-setted.
Since the override command is only accessible to authorised maintenance personnel. the operator cannot access the overrides command and he started to panic
Wednesday, April 24, 2013
The Logic Behind The Magic. “Emergency Shutdown System (ESD) Operating Philosophy 3"
Start-up and Maintenance
inhibit/ Override
In order
to be able to start-up equipment or sections process, it is necessary to
inhibit some inputs to the ESD system, as sensor signal may be in abnormal
state prior to start-up and could cause a shutdown. Such inhibits are
designated as "start-up inhibits".
While Maintenance inhibits are set from the maintenance
/ inhibit console for maintenance purpose
Each
inhibit function is reset automatically either by the sensor signal reverting
to normal state or after a predetermined time delay. The automatic resets are
achieved by the Safety Shutdown System.
The Logic Behind The Magic. “Emergency Shutdown System (ESD) Operating Philosophy 2"
Resetting philosophy
Further to
a shutdown, the related ESD levels need to be individually and manually reset
by the Operation Console operator. The ESD level can be reset only if the upper ESD level is
in normal condition.
Resetting
sequence is as follows :
·
The
operator is informed on the ESD and process displays that the ESD level can be
reset
·
ESD
level alarm return to normal conditions only when all ESD causes have
disappeared or have been inhibited and the ESD level reset is carried out on
the ESD display of theOperation Console
The Logic Behind The Magic. “Emergency Shutdown System (ESD) Operating Philosophy 1"
The Emergency Shutdown (ESD) System is designed to protect the personnel, plant, equipment and the
environment against pollution. The purpose of the ESD system is to monitor
process safety parameters and activate or shutdown the process system and/or
the utilities if these parameters deviate from normal conditions.
Usually there are
several levels of shutdown:
·
ESD 0
: Total emergency
shutdown with abandon of platform
·
ESD
0.1 : Black shutdown
·
ESD 1
: Total plant
emergency shutdown
·
ESD 2
: Total process
shutdown
·
ESD 3
: Local unit
shutdown