BDV is typically with shutdown valve but in the reverse condition.(BDV is Fail Open valve, SDV is Fail Closed valve)
These type of valves usually have 3 signals output and 8 input status that are shown in the control room,
Input:
- Group Reset
- keyswitch BDV
- open command
- Logic command not trip
- close limit sw
- not open limit sw (not close)
- Timer SP
- Valve Command "Close"
- Logic status "Trip"
- Discrepancy alarm
- If the logic command trip, logic status trip will be activated
- The valve cannot be closed until SDV switch, open command and Logic command trip deactivated and Group reset command becomes active.
- If valve is in open condition but limit switch closed active, Discrepancy alarm shall be activated
- If valve is in close condition but limit switch open active, Discrepancy alarm shall be activated