Open Path type gas detector devices measure the sum of the hydrocarbon molecules along a narrow
beam, the configuration for displaying the reading from an IR beam gas detector
is as follows:
Display in LEL-meters which is an integral of percentage LEL as
multiplied by the length of the beam.
This is in effect a direct reading of what the device is measuring i.e.
the total number of hydrocarbon molecules along the length of the beam.
·
High-High level gas – 2.53
LEL.m
- 2-60Hz maximum Peak to Peak amplitude vibration
- Diagnostic capabilities, to alert incorrect installation and fault conditions
- Loss of signal strength of <5 for="">60minutes shall indicate a fault.5>
- Detectors are double pass filtered to compensate for fog, rain and mist interference.
- Misalignment tolerance of 0.25°. Both vertical and horizontal adjustment of 45°, with locking facility shall be provided. Beam misalignment of 1° or less is not adversely affect performance.
- Error range shall not be exceeded while any one or more interference mechanisms are present.
- The speed of response shall not exceed 5 seconds for the specified beam path length, T90 less than 3 secs.
- The detector will be calibrated on methane with a measurement range of 0 to 5 LEL.m for methane with the output being 4mA for 0 LEL.m and 20mA for 5 LEL.m.
These type of detector usually have 7 signals and status
that are shown in the control room,
- Faulty Status
- Calibrate alarm
- Beam Block alarm
- High gas exec action
- High-high alarm
- High-high gas exec action.
- Inhibit signal
The
logic are:
- If the detector is in the faulty status (open loop or short). Exec. Action trip command and alarm will be deactivated until the reset command is activated.
- If the gas detector is in calibration mode. Beam block alarm will be deactivated until the reset command is activated.
- If the detector is in the inhibit status. None of the other signals will be executed until the reset command is activated.
- If the High gas alarm (1 LEL.m) detected. High gas exection trip will be activated until the reset command is activated.
- If the High-high gas alarm (2.5 LEL.m) detected. High-high gas exection trip will be activated until the reset command is activated
No comments:
Post a Comment