Resetting philosophy
Further to
a shutdown, the related ESD levels need to be individually and manually reset
by the Operation Console operator. The ESD level can be reset only if the upper ESD level is
in normal condition.
Resetting
sequence is as follows :
·
The
operator is informed on the ESD and process displays that the ESD level can be
reset
·
ESD
level alarm return to normal conditions only when all ESD causes have
disappeared or have been inhibited and the ESD level reset is carried out on
the ESD display of theOperation Console
Field equipment reset
Unless
otherwise specified, SDVs/BDVs valves are locally manually reset.
Resetting
sequence is as follows :
·
ESD
logic is reset at Operation Console
·
Valve
is manually reset (permissive reset)
·
Valve
is actuated at Operation Console
Local
permissive resets are input to the ESD system.